Re: Crane tankless disconnect


[ Follow Ups ] [ Post Followup ] [ Boiler Room Residential and Home Forum #4 ] [ FAQ ]

Posted by heatpro.us on March 02, 2012 at 14:46:02:

In Reply to: Re: Crane tankless disconnect posted by Mike on March 02, 2012 at 13:23:57:

The temperature control to fire the burner is an electronic control with a dial.

Drain the lines and the tank and disconnect them from the boiler. Can't see how the lines were connected from here. If there's a steam line to the tank cap that off on the boiler side. Unless the lines leak water, don't cap them on the boiler side. Cap them on the feedwater side.

There are some older wiring diagrams in the PDF downloads at
http://www.livepast60.com/heatpro/oilbooks.htm