Re: Steam Boiler Glass Sight FULL


[ Follow Ups ] [ Post Followup ] [ Boiler Room Residential and Home Forum #4 ] [ FAQ ]

Posted by HeatPro on November 17, 2008 at 07:12:52:

In Reply to: Steam Boiler Glass Sight FULL posted by Mark on November 17, 2008 at 05:44:12:

the system then seems to feed new water in

How does it do that? Is there an automatic water feeder? If so, that is one cause of the problem. Incorrect setting or a leaking solenoid feed valve can allow too much water in. Close the hand valve to the feeder and observe the result. Then tell us.