Re: New GAs Boiler creates Loud Banging and Significant water leak...


[ Follow Ups ] [ Post Followup ] [ Boiler Room Residential and Home Steam-Forum ] [ FAQ ]

Posted by jtown on January 02, 2000 at 09:53:34:

In Reply to: Re: New GAs Boiler creates Loud Banging and Significant water leak... posted by Jenny on January 01, 2000 at 15:30:48:

You checked the pitch of the radiator. Did you check the pitch of all the piping back to the boiler? Use a level and rotate it on a flat surface so you know it isn't off. Is this radiator at the end of a main? Is there one upstairs or downstairs on the same riser? Is there any long horizontal piping on the way to it?