Posted by HeatPro on December 28, 2008 at 21:46:44:
In Reply to: Re: Heatmaker hotwater/heat posted by John G on December 28, 2008 at 19:40:22:
: : You are getting a delayed ignition pop. Have it serviced, gas is accumulating before it becomes lit. There can be a number of causes that need be checked.
: Thanks Heat-Pro: Are you saying that un-burned natural gas is accumulating somewhere in the burner section of the boiler which has been burning for some 20mins?
+++ No I wrote what I said above. You are saying that.
It is more likely the unit goes through a heat cycle, shuts off on a limit or on a cycle and pops on the relight.