Posted by HeatPro on December 04, 2007 at 15:05:07:

In Reply to: RA889A posted by Mark Bassin on December 04, 2007 at 13:58:47:

The diagrams:
http://customer.honeywell.com/honeywell/ProductInfo.aspx/RA889A1001#LiteratureDownload

show that X1 and X2 would close to activate a millivolt system. An ohmmeter would show that they close if all is working properly when R(T) and W(T ) are jumped.

If there is no action, something is broken.