Re: Steam baseboard or other alternative


[ Follow Ups ] [ Post Followup ] [ Boiler Room Residential and Home Steam-Forum ] [ FAQ ]

Posted by Harold Kestenholz - Hydronic Network on April 16, 2001 at 10:28:41:

In Reply to: Steam baseboard or other alternative posted by Peter Lothian on April 14, 2001 at 16:14:35:

An old installers technique was to use fin tube that fits under the cabinet and use expanded metal mesh or louvered covers to allow the air to enter and leave the element. As the heat will be supplied by steam, use the larger (over 1-inch size) fin tube and make sure the tube has a slight slope toward the return to the boiler so the water doesn't collect to bang.