Re: Taco Mixing Valve thermosiphoning


[ Follow Ups ] [ Post Followup ] [ Boiler Room Residential and Home Forum #3 ] [ FAQ ]

Posted by HeatPro on April 06, 2007 at 14:52:28:

In Reply to: Taco Mixing Valve thermosiphoning posted by Ronald G. Scalzo on March 21, 2007 at 23:13:45:

a good 8' run in 3/4" pipe
is a cause of thermo-siphoning. A U-trap made from the 3/4 tubing from the indirect hot water outlet toward the floor 3-feet and then rising to the cold water source would prevent thermo-siphoning.