Re: Can I overcome a radiator/piping size mismatch?


[ Follow Ups ] [ Post Followup ] [ Boiler Room Residential and Home Forum #2 ] [ FAQ ]

Posted by HeatPro on December 02, 2005 at 14:14:37:

In Reply to: Can I overcome a radiator/piping size mismatch? posted by Jeremy on December 02, 2005 at 13:52:06:

A reducing coupling from the valve connection nipple for the radiator to a 1-inch close nipple to the radiator will do it. The idea is that the pipe slope fall from the radiator to the valve, so the water can fall back out without a water dam to hold it in the radiator or connection locations.