Re: Caps inslalled on boiler stacks.


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 3 ] [ FAQ ]

Posted by Danny on June 29, 2005 at 08:35:59:

In Reply to: Re: Caps inslalled on boiler stacks. posted by tm on June 22, 2005 at 08:57:10:

We retrofitted two 150klb/hr, 400# steam, gas fired boilers with hats over the stacks for protection from rain. Our issue was that rain events would swing boiler stack instrumentation enough to upset the boiler. I had not heard of any regulations, but it is a good idea to check. Boilers are in the Houston, TX area.