Deaerator vent spewing water slugs


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]

Posted by George Larose on November 09, 2001 at 18:38:56:

I have a deaerator application ( a normal spray type deaerator) in which the non-condensible gas vent spews slugs of water from time to time, seemingly when admitting proportionally more cold make-up water. The deaerator operating pressure is 6-7 psig, the vent is a 1" gate valve with a 5/32-inch hole drilled in the gate, and the valve is shut, allowing a plume of 18-24" of vapour. Ideas, please?


Follow Ups:



Post a Followup

Name:
E-Mail:

Subject:

Comments:


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]