[an error occurred while processing this directive]
Posted by Mark on May 18, 2005 at 19:56:14:
In Reply to: Re: Burnham V35 OEM specs and/or settings posted by HeatPro on May 07, 2005 at 15:12:52:
Thanks for the info. I was hoping to locate some literature or information. After some good old trial and error I ended up with the following results; Delavan nozzle 1.25 80 SS fired at 100 p.s.i. through an F3 head. I also verified "Z-dimension" & insertion depth of the blast tube. being that this was a retro-fit application, sealing the burner mountinting flange from unwanted secondary air was also key. I did, however end up with an 11% CO2 w/0 smoke.